MAINLY UNIT FEATURE OF SCREW COMMPRESSOR
Superior performance
- Adoption international advanced third generation 5: 6 semi-hermestic screw compressor, the motor and compressor integration, without seal leakage concerns
- Two or a plurality of compressor combination precision control program is reasonable and balanced the handpiece assembly load, prolong the service life of the unit
- Two or a plurality of compressor using multiple sets of refrigeration circuit, when a circuit must be repaired and maintenance, the remaining loop can still be operated normally, with standby function
- Compressor with duplex winding reduced-voltage starting, avoid the impact to the electric network
Easy Installation
- Compact structure, small occupation area, saving the space
- The machine has been checked ststrictly and timing operation completed to reach the using state
- Based minimum vibration, don't need the vibration isolation equipment usually, simple installation
- Just need connect with the cooling water chilled water pipe of evaporator and condenser
Low cost for operation and maintenance
- Unit can be controled by intelligent program according to the load needs: 0-25-50-75-100% volume control to save energy.
- Screw compressor has simple structure, few wearing parts, the failure rate is very low
- The built-in oil separator using three stage oil filter; Adoption the coating design to reduce the compressor'noise
- Water chiller compressor trouble-free operation over 40000 hours
Complete security protection function
- High & low pressure protection
- Anti-heatingsafety valve
- Anti freezing protection
- Overload protection,
- Incomplete phase protection
- Opposite phase protection
- lacking voltage and over voltage protection
- Water flow protection
Humanized microcomputer control system
- Adoption brand-name PLC liquid crystal color LED display, touch panel computer control, the Chinese interface for simple operation
- Automatic detect outlet temperature of chilled water system, effective tracking site load by adjusting the compressor
- The display is intuitive, can be readily read operation data for reference
- Automatic failure alarm system can display the failure code to handle
- Output feedback information to the other main control system based on the needs of field
- The original content can be modified based on the field needs, such as position of each unit, protection, pressure etc.
Application of the strong widely
- Widely used in rubber, plastic, petroleum, chemical, electronics, textile, papermaking, brew, pharmaceutical, machinery, food, beverage, vacuum coating, plating, coating, central air-conditioning and other fields
-This machine series is widely applied in the centralized cooling way
- This machine can be customized for the acid and alkali resistant special models, the special needs of customers with special process
- This machine can be customized for low temperature type special models using the low temperature cold medium, to reach the customer special technology of special needs.
Model | 100WSEC | 140WSEC | 180WSEC | 200WSEC | 250WSEC | 270WSEC | 310WSEC | 360WSEC | 380WSEC | 410WSEC | |
Rated Refrigeration capacity | KW | 20 | 27 | 34 | 38 | 46 | 56 | 62 | 67 | 72 | 79 |
x10 3 KCal/hr | 16 | 21 | 26 | 32 | 39 | 53 | 53 | 57 | 62 | 68 | |
Compressor Power (KW) | 18 | 24 | 32 | 38 | 47 | 58 | 73 | 74 | 78 | 81 | |
running current(A) | 31 | 41 | 54 | 64 | 79 | 98 | 124 | 126 | 132 | 137 | |
Capacity Control(%) | 0-33-66-100 | 0-25-50-75-100 | |||||||||
Condenser | shell and tube type | ||||||||||
Condenser import and outlet diameter(inch) | 2" | 2" | 2" | 2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 3" | |
Cooling water flow(m 3 /h) | 6 | 8 | 11 | 13 | 16 | 19 | 23 | 24 | 26 | 27 | |
Evaporator | shell and tube type | ||||||||||
Evaporator import and outlet diameter(inch) | 2" | 2" | 2" | 2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | |
30% Glycol flow capacity (m3/h) | 4 | 5 | 6 | 8 | 9 | 11 | 12 | 13 | 14 | 16 | |
safety protection device | High & low pressure protection,anti-freezing protection,anti-heating safety valve,overload protection,incomplete phase protection,opposite phase protection,lacking voltage and over voltage protection,water flow protection | ||||||||||
Out dimension | L(mm) | 1989 | 2042 | 2313 | 2313 | 1820 | 3100 | 3100 | 3100 | 3100 | 3100 |
W(mm) | 850 | 850 | 850 | 850 | 850 | 1200 | 1200 | 1200 | 1200 | 1200 | |
H(mm) | 1350 | 1350 | 1350 | 1390 | 1390 | 1500 | 1700 | 1700 | 1860 | 1860 | |
Total weight | Kg | 850 | 850 | 1050 | 1270 | 1430 | 1740 | 2280 | 2480 | 2600 | 2870 |
Working weight | Kg | 900 | 900 | 1100 | 1420 | 1560 | 1890 | 2380 | 2580 | 2800 | 3120 |
Model | 480WSEC | 510WSEC | 580WSEC | 610WSEC | 670WSEC | 720WSEC | 760WSEC | 810WSEC | 850WSEC | 940WSEC | |
Rated Refrigeration capacity | KW | 95 | 101 | 116 | 123 | 135 | 145 | 151 | 163 | 171 | 190 |
x10 3 KCal/hr | 82 | 86 | 100 | 106 | 116 | 125 | 130 | 140 | 147 | 164 | |
Compressor Power (KW) | 92 | 99 | 111 | 121 | 132 | 140 | 150 | 155 | 157 | 170 | |
running current(A) | 156 | 168 | 189 | 206 | 225 | 237 | 276 | 290 | 267 | 289 | |
Capacity Control(%) | 0-25-50-75-100 | ||||||||||
Condenser | shell and tube type | ||||||||||
Condenser import and outlet diameter(inch) | 3" | 3" | 3" | 4" | 4" | 4" | 4" | 4" | 4" | 4" | |
Cooling water flow(m 3 /h) | 32 | 34 | 39 | 42 | 46 | 49 | 54 | 57 | 59 | 62 | |
Evaporator | shell and tube type | ||||||||||
Evaporator import and outlet diameter(inch) | 2-1/2" | 2-1/2" | 3" | 3" | 3" | 3" | 3" | 3" | 3" | 4" | |
30% Glycol flow capacity (m3/h) | 19 | 20 | 23 | 25 | 27 | 29 | 31 | 33 | 34 | 38 | |
safety protection device | High & low pressure protection,anti-freezing protection,anti-heating safety valve,overload protection,incomplete phase protection,opposite phase protection,lacking voltage and over voltage protection,water flow protection | ||||||||||
Out dimension | L(mm) | 3135 | 3135 | 3200 | 3275 | 3300 | 3300 | 3300 | 3300 | 3300 | 3300 |
W(mm) | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | |
H(mm) | 2000 | 2000 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | |
Total weight | Kg | 3150 | 3250 | 3400 | 3600 | 4300 | 4345 | 4400 | 4455 | 4510 | 4620 |
Working weight | Kg | 3450 | 3550 | 3700 | 3900 | 4550 | 4640 | 4700 | 5760 | 4820 | 4940 |
Model | 200WDEC | 280WDEC | 320WDEC | 360WDEC | 400WDEC | 440WDEC | 480WDEC | 530WDEC | 580WDEC | 620WDEC | 660WDEC | 700WDEC | 740WDEC | 800WDEC | 880WDEC | |
Rated Refrigeration capacity | KW | 38 | 50 | 61 | 68 | 76 | 84 | 93 | 103 | 113 | 119 | 125 | 134 | 145 | 159 | 175 |
x10 3 KCal/hr | 33 | 43 | 52 | 58 | 65 | 72 | 80 | 89 | 97 | 102 | 108 | 115 | 125 | 137 | 151 | |
Compressor Power (KW) | 37 | 49 | 64 | 71 | 77 | 86 | 94 | 106 | 117 | 132 | 147 | 149 | 157 | 162 | 174 | |
running current(A) | 62 | 84 | 109 | 119 | 130 | 145 | 159 | 178 | 197 | 223 | 248 | 252 | 265 | 274 | 294 | |
Capacity Control(%) | 0-33-66-100 | 0-25-50-75-100 | ||||||||||||||
Condenser | shell and tube type | |||||||||||||||
Condenser import and outlet diameter(inch) | 2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 3" | 3" | 3" | 4" | 4" | 4" | 4" | 4" | 4" | |
Cooling water flow(m 3 /h) | 14 | 18 | 22 | 24 | 27 | 30 | 33 | 36 | 40 | 44 | 47 | 49 | 52 | 56 | 60 | |
Evaporator | shell and tube type | |||||||||||||||
Evaporator import and outlet diameter(inch) | 2" | 2" | 2" | 2" | 2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | 3" | 3" | 3" | |
30% Glycol flow capacity (m3/h) | 8 | 11 | 13 | 15 | 16 | 18 | 20 | 22 | 24 | 25 | 26 | 28 | 30 | 33 | 36 | |
safety protection device | High & low pressure protection,anti-freezing protection,anti-heating safety valve,overload protection,incomplete phase protection,opposite phase protection,lacking voltage and over voltage protection,water flow protection | |||||||||||||||
Out dimension | L(mm) | 3380 | 3380 | 3480 | 3480 | 3480 | 3790 | 3790 | 3790 | 3790 | 3790 | 3860 | 3860 | 3860 | 3900 | 3900 |
W(mm) | 910 | 910 | 1110 | 1110 | 1310 | 1310 | 1310 | 1310 | 1310 | 1310 | 1310 | 1310 | 1310 | 1510 | 1510 | |
H(mm) | 1450 | 1450 | 1550 | 1590 | 1770 | 1980 | 1980 | 1980 | 1990 | 1990 | 2010 | 2010 | 2010 | 2280 | 2280 | |
Total weight | Kg | 1670 | 1870 | 2320 | 2420 | 3020 | 3520 | 3820 | 3820 | 4020 | 4420 | 4520 | 5320 | 5720 | 5920 | 6070 |
Working weight | Kg | 1920 | 2170 | 2570 | 2770 | 3570 | 4020 | 4370 | 4370 | 4620 | 4970 | 4970 | 6070 | 6320 | 6520 | 6720 |
Model | 960WDEC | 1020WDEC | 1090WDEC | 1160WDEC | 1220WDEC | 1340WDEC | 1390WDEC | 1440WDEC | 1520WDEC | 1570WDEC | 1620WDEC | 1700WDEC | 1760WDEC | 1820WDEC | 1880WDEC | |
Rated Refrigeration capacity | KW | 191 | 202 | 218 | 233 | 248 | 271 | 281 | 292 | 304 | 315 | 326 | 342 | 357 | 371 | 381 |
x10 3 KCal/hr | 164 | 174 | 187 | 200 | 213 | 233 | 242 | 251 | 261 | 271 | 280 | 294 | 307 | 319 | 328 | |
Compressor Power (KW) | 185 | 199 | 211 | 223 | 244 | 266 | 273 | 280 | 286 | 301 | 311 | 315 | 324 | 333 | 342 | |
running current(A) | 314 | 337 | 358 | 378 | 413 | 451 | 463 | 475 | 553 | 567 | 581 | 534 | 549 | 564 | 579 | |
Capacity Control(%) | 0-25-50-75-100 | |||||||||||||||
Condenser | shell and tube type | |||||||||||||||
Condenser import and outlet diameter(inch) | 4" | 5" | 5" | 5" | 5" | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | 4"x 2 | |
Cooling water flow(m 3 /h) | 65 | 69 | 74 | 79 | 85 | 93 | 96 | 99 | 109 | 112 | 115 | 113 | 117 | 121 | 125 | |
Evaporator | shell and tube type | |||||||||||||||
Evaporator import and outlet diameter(inch) | 3" | 3" | 3" | 4" | 4" | 4" | 4" | 4" | 4" | 5" | 5" | 5" | 5" | 5" | 5" | |
30% Glycol flow capacity (m3/h) | 39 | 42 | 45 | 48 | 51 | 55 | 58 | 60 | 62 | 64 | 67 | 70 | 73 | 76 | 78 | |
safety protection device | High & low pressure protection,anti-freezing protection,anti-heating safety valve,overload protection,incomplete phase protection,opposite phase protection,lacking voltage and over voltage protection,water flow protection | |||||||||||||||
Out dimension | L(mm) | 3900 | 3900 | 3900 | 3900 | 3900 | 3900 | 3900 | 3900 | 4410 | 4410 | 4410 | 4410 | 4410 | 4410 | 5010 |
W(mm) | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1510 | 1810 | |
H(mm) | 2280 | 2280 | 2280 | 2280 | 2280 | 2280 | 2280 | 2280 | 2290 | 2290 | 2290 | 2290 | 2290 | 2290 | 2510 | |
Total weight | Kg | 6170 | 6220 | 6270 | 6320 | 6720 | 7020 | 7120 | 7220 | 7420 | 7540 | 7640 | 7880 | 7930 | 8030 | 8230 |
Working weight | Kg | 6870 | 6820 | 6870 | 6920 | 7420 | 7620 | 7720 | 7920 | 8120 | 8220 | 8360 | 8520 | 8700 | 8800 | 8970 |
Remark: | ||||||||||||||||
1.The above power supplier is 3P-380V-50HZ,permission voltage hunting±10% ,pemission internce±2% . | ||||||||||||||||
2.The above nominal capacity is based on chilling water inlet temperature at -30°C,outlet temperature at -35 °C,cooling water temperature at 30°C,and outlet temperature at 35°C. | ||||||||||||||||
3.Equipment safe working range :Chilled water inlet temperature of -35~-25ºC | ||||||||||||||||
4.This series of unit adopts imported temperature controller or PLC controllers; | ||||||||||||||||
5.If specification is changed, then the actual model shall govem. |